Floor Plan - Lighting
- Coordinate with Architectural Floor Plans and Reflected Ceiling Plans.
- Indication of North.
- "Drawing Title Designation" for Floor Plan.
- Reference items on Lighting Plans to the details of these items appearing on other sheets.
- Include a note to read: "See sheet __ (Information Sheet) for clarification of Symbols used." List any additional Symbols on Electrical Sheets.
- Column Reference Grids:
- Coordinate with Architectural Floor Plans and Reflected Ceiling Plans.
- Room Names and Numbers:
- Coordinate with Architectural Floor Plans.
- All Fixtures indicated with appropriate "F" designation.
- Locate, by dimension, all Exterior Lighting Fixtures in Parking Areas and on Exterior Building Walls and Interior Fixtures no related to the Grid System.
- Fixture Schedule with Pictorial Views adjacent to the Schedule.
- Mounting heights for all Fixtures (may be combined with Fixture Schedule).
- Door Swings shall match Architectural Floor Plans.
- Coordinate Wall Switches with Door Swings.
- Check for conflicts between recessed Fixtures and Ductwork, Piping, etc.
- Coordinate location of Lighting Panels with Power Panels, Emergency Panels, etc. and coordinate with Panelboard Schedules.
- Indicate location of Dimmers.
- Lighting Fixture installation details, especially for Exterior Fixtures.
- Check clearances and location of Suspended Fixtures where Roll-up Doors occur.
- Coordinate Fixture installation with U.L. Systems selected.
- Use "Reference Designation" (hexagon) for repetitive items with a legend of "Clarification of Reference Designations."
- Indicate Fixtures on Emergency Circuits.
- Coordinate Ceiling Finishes with Fixtures specified.
- Coordinate special Lighting, Junction Boxes, etc. for Millwork with Architectural Millwork Details.
- Coordinate Fixtures selected with type of Ceiling being used ( concealed spline, exposed grid, etc.)
- Check codes for Exterior Lighting required at all "required means of egress." Must be on emergency circuit.
- Cross Corridors, double egress Doors forming smoke barriers on horizontal exits require Exit signs on both sides of Doors.
- Refer to "Reflected Ceiling Plan" for exact locations of items in or on ceiling.
- Coordinate the location of Exit lights at Doors.